Skip to main content

Table 7 10-bus distribution network system data

From: An efficient load flow solution for distribution system with addition of distributed generation using improved harmony search algorithms

Line no.

Node i

Node j

Resistance

R (Ω)

Reactance

X (Ω)

Load at the receiving node

P (kW)

Q (kVAr)

1

1

2

0.1233

0.4127

1840

460

2

2

3

0.0140

0.6057

980

340

3

3

4

0.7463

1.2060

1790

446

4

4

5

0.6984

0.6084

1598

1840

5

5

6

1.9831

1.7276

1610

600

6

6

7

0.9053

0.7886

780

110

7

7

8

2.0552

1.1640

1150

60

8

8

9

4.7953

2.7160

980

130

9

9

10

5.3434

3.0264

1640

200

  1. Base MVA = 100, base kV = 23