Skip to main content

Table 1 Comparison of impulse impedance for single vertical rod with and without consideration of mutual coupling

From: Analysis of grounding system transient with consideration of soil ionization and mutual coupling effect

Current peak (kA)

Soil resistivity

\(\rho =\) 50 Ω m

\(\rho =\) 100 Ω m

\(\rho =\) 500 Ω.m

Impulse impedance (Ω)

Relative difference (in %)

Impulse impedance (Ω)

Relative

Difference (in %)

Impulse impedance (Ω)

Relative difference (in %)

With

mutual coupling

Without mutual coupling

With

mutual coupling

Without mutual coupling

With mutual coupling

Without mutual coupling

10

10.51

10.00

4.85

21.00

20.20

3.81

67.00

65.00

2.98

20

8.50

8.00

5.88

16.60

15.80

4.82

47.00

45.00

4.25

50

6.40

6.00

6.25

12.70

12.00

5.51

34.80

33.00

5.17

100

5.42

5.00

7.75

11.00

10.20

7.27

30.00

28.40

5.33