From: Power management scheme development for large-scale solar grid integration
Bus | V/Vn (%) of 9 bus | V/Vn (%) of 9 bus with solar | V/Vn (%) of 9 bus after Optimal capacitor placements | V/Vn (%) of 9 bus after volt-var Q(U) regulation | V/Vn (%) of 9 bus after volt-var regulation Q(U) and optimal capacitor placements |
---|---|---|---|---|---|
1 | 91.246 | 87.827 | 99.014 | 93.318 | 100.502 |
2 | 100 | 100 | 100 | 100.000 | 100.000 |
3 | 89.768 | 86.115 | 96.638 | 92.000 | 98.253 |
4 | 89.096 | 85.612 | 97.002 | 91.206 | 98.514 |
5 | 87.223 | 83.974 | 94.94 | 89.284 | 96.375 |
6 | 87.224 | 83.414 | 95.481 | 89.442 | 97.110 |
7 | 94.583 | 92.468 | 98.306 | 95.935 | 99.270 |
8 | 91.763 | 88.567 | 96.683 | 93.808 | 98.157 |
9 | 91.051 | 87.48 | 97.581 | 93.238 | 99.165 |