Skip to main content

Table 3 Results of the dynamic reconfiguration of the IEEE 15- node system

From: A novel approach of a dynamic multi objective optimization of a power distribution system

Period

Active power load (kW)

SAIFI (failure/day)

Without reconfiguration

After reconfiguration

Active power losses (kW)

SAIDI (h/day)

Open switches

Vmin (p.u.)

Vde (p.u.)

Active power losses (kW)

SAIFI (fail./day)

Open switches

Vmin (p.u.)

Vde (p.u.)

SAIDI (h/day)

1

4554.0

1

0*

1

No

0*

1*

80.169

0.571

S2

0.9455

0.0545

0.571

2

4305.0

0

384.67

0

No

0.8752

0.1248

66.937

0.571

S2

0.9508

0.0492

0.571

3

3876.0

0

312.27

0

No

0.8874

0.1126

56.431

0.571

S2

0.9548

0.0452

0.571

4

3326.0

0

230.35

0

No

0.9030

0.0970

230.35

0

No

0.9030

0.0970

0

5

3205.0

0

213.98

0

No

0.9065

0.0935

213.98

0

No

0.9065

0.0935

0

6

3693.0

0

283.65

0

No

0.8925

0.1075

50.779

0.571

S2

0.9571

0.0429

0.571

7

7542.0

1

0*

1

No

0*

1*

204.39

0.571

S2

0.9141

0.0859

0.571

8

7909.0

1

0*

1

No

0*

1*

229.48

0.571

S2

0.9090

0.0910

0.571

9

8279.0

1

0*

1

No

0*

1*

232.13

0.571

S2

0.9086

0.0914

0.571

10

6067.0

1

0*

1

No

0*

1*

137.05

0.571

S2

0.9296

0.0704

0.571

11

9369.0

1

0*

1

No

0*

1*

278.41

0.571

S2

0.9000

0.1000

0.571

12

9054.0

1

0*

1

No

0*

1*

276.88

0.571

S2

0.9001

0.0999

0.571

13

8823.0

1

0*

1

No

0*

1*

265.53

0.571

S2

0.9022

0.0978

0.571

14

8823.0

1

0*

1

No

0*

1*

265.53

0.571

S2

0.9022

0.0978

0.571

15

7670.0

1

0*

1

No

0*

1*

205.74

0.571

S2

0.9139

0.0861

0.571

16

9801.0

1

0*

1

No

0*

1*

280.96

0.571

S2

0.9000

0.1000

0.571

17

7440.0

1

0*

1

No

0*

1*

201.46

0.571

S2

0.9148

0.0852

0.571

18

7049.0

1

0*

1

No

0*

1*

187.44

0.571

S2

0.9178

0.0822

0.571

19

7317.0

1

0*

1

No

0*

1*

196.50

0.571

S2

0.9157

0.0843

0.571

20

6643.0

1

0*

1

No

0*

1*

156.41

0.571

S2

0.9248

0.0752

0.571

21

5651.0

0

659.79

0

No

0.8378

0.1622

125.52

0.571

S2

0.9326

0.0674

0.571

22

5163.0

0

551.68

0

No

0.8513

0.1487

102.38

0.571

S2

0.9391

0.0609

0.571

23

4793.0

0

476.04

0

No

0.8616

0.1384

85.872

0.571

S2

0.9443

0.5570

0.571

24

4554.0

0

430.09

0

No

0.8683

0.1317

82.169

0.571

S2

0.9455

0.0545

0.571

Total

–

15

3542.52

15

–

–

–

4212.49

12.56

–

–

–

12.56

Average

–

0.625

147.605

0.625

–

–

–

175.52

0.523

–

  

0.523

  1. *This situation is due to the fact that there is an interruption in the supply of electrical energy because the available power is insufficient