Parameter | Without HPC losses (WOHPCL) | With HPC losses (WHPCL) | ||||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
Base Case | NM [27] | PSO [22] | CS [27] | HNMCS [27] | BOA CASE-1 | BOA CASE-2 | Base Case | BOA CASE-2 | ||||||||
REDG@7 | REDG@26 | REDG@7 | REDG@26 | REDG@7 | REDG@26 | REDG@7 | REDG@26 | REDG@7 | REDG@26 | REDG@13 | REDG@30 | REDG@12 | REDG@30 | |||
Solar-PV optimal area (m2) | Â | 5278.56 | 1278.56 | 5000.83 | 4295.87 | 2747.71 | 4583.19 | 2191.53 | 2675.18 | 2332.7 | 1361 | 1678 | 1507.8 | Â | 895.3438 | 664.5533 |
Solar-PV optimal power required (kW) | Â | 639.76 | 156.80 | 606.10 | 520.66 | 333.02 | 555.48 | 265.61 | 324.23 | 283 | 165 | 203 | 183 | Â | 108.5157 | 80.5439 |
FC optimal area (m2) | Â | 306.36 | 584.93 | 301.82 | 261.18 | 414.73 | 246.72 | 442.45 | 342.32 | 435.4 | 408.1 | 265.4 | 392.4 | Â | 355.4116 | 395.3083 |
FC optimal power required (kW) | Â | 739.30 | 1416.20 | 730.74 | 632.34 | 1004.11 | 597.33 | 1071.22 | 828.81 | 1054 | 988 | 643 | 950 | Â | 860.4901 | 957.0845 |
Total area required (m2) | Â | 7462.57 | Â | 9859.70 | Â | 7992.35 | Â | 5651.49 | Â | 4537.2 | Â | 3843.6 | Â | Â | 2310.6 | Â |
Total power loss (kW) | 139.7 | 48.33 | Â | 47.52 | Â | 46.07 | Â | 46.07 | Â | 46.0532 | Â | 26.8325 | Â | 171.7 | 27.3390 | Â |
Power loss reduction (%) | Â | 65.45 | Â | 66.0 | Â | 67.0 | Â | 67.07 | Â | 67.05 | Â | 80.80 | Â | Â | Â | Â |
Convergence time (s) | Â | 1.06 | Â | 12.61 | Â | 9.22 | Â | 8.86 | Â | 7.05 | Â | 8.27 | Â | Â | 7.14 | 8.54 |
Number of PV panels | Â | 320 | 77 | 303 | 260 | 167 | 278 | 133 | 163 | 142 | 83 | 102 | 92 | Â | 54 | 40 |
Number of FC | Â | 29 | 56 | 29 | 25 | 39 | 23 | 43 | 33 | 42 | 39 | 26 | 38 | Â | 34 | 38 |