Table 4 System response for step change in load, pertaining to case 2

From: A novel computational technique using coefficient diagram method for load frequency control in an interconnected power system

Method

Δf1

Δf2

ΔPtie

ts(t)

US

OS

IAE(× 10–3)

ts(t)

US

OS

IAE(× 10–3)

ts(t)

US

OS

IAE(× 10–3)

CDM-OPT

6.71

2.907e−04

−4.508e−03

2.179

6.55

2.711e−04

−2.480e−03

2.083

3.87

0.3647e−04

−0.8345e−03

0.677

PID

8.41

6.549e−04

−5.287−04

3.278

9.7

6.394–04

−3.313e−03

3.161

6.42

1.032e−04

−1.131e−03

0.960

Fuzzy

6.5

11.50e-04

7.701e−04

3.631

6.33

N.O

−5.381e−03

3.246

3.87

N.O

−1.741e−03

0.687

CDM

30 > 

N.O

−10.89e−03

55.08

30 > 

N.O

−10.42e−03

55.07

30 > 

N.O

−3.544e−03

20.12

PI

30 > 

27.3e-04

−19.33e−03

73.25

30 > 

17.25e-04

−23.97e−03

63.47

30 > 

16.25e−04

-9.005e-03

31.39