Skip to main content

Table 3 Summary of the obtained temperature from experimental and simulation results of tested cable

From: The effect of nonlinear loads on the underground distribution cables: a case study

 

Experimental results

Simulation results

Cable installed direct buried in the soil

Maximum insulation temperature (°C)

Without harmonic

65

68

With harmonic

72

74

Maximum jacket temperature (°C)

Without harmonic

57

60

With harmonic

64

66

Maximum soil temperature (°C)

Without harmonic

52

54

With harmonic

56

58

Cable installed in PVC duct and buried in the soil

Maximum insulation temperature (°C)

Without harmonic

70

73

With harmonic

77

80

Maximum jacket temperature (°C)

Without harmonic

63

65

With harmonic

68

71

Maximum soil temperature (°C)

Without harmonic

33.5

34

With harmonic

35.5

36.5