Skip to main content

Table 2 Current and total harmonic distortion on each phase

From: The effect of nonlinear loads on the underground distribution cables: a case study

Phase

Current (A)

Without harmonic loads

With harmonic loads

Loads types

THD %

Loads types

Source

THD %

A

18.22

Resistance banks

4.35

Fluorescent lamps

Single

50.8

One branch of resistance bank

Single

Adjustable speed drive

Three

B

18.78

Resistance banks

4.35

Auto-transformer

Single

34.4

Two branches of resistance bank

Single

Adjustable speed drive

Three

C

18.32

Resistance banks

4.35

Power supply

Single

44.8

Tungsten coils

Single

Adjustable speed drive

Three