Table 1 Cable characteristics

From: The effect of nonlinear loads on the underground distribution cables: a case study

Characteristic

Value

Unit

Long of cable used

1

m

Cross-section area of an aluminum conductor

16

\({mm}^{2}\)

Nominal thickness of insulation

0.7

mm

Nominal thickness of outer PVC sheath

1.8

mm

Overall diameter of cable

19

mm

Permissible operating temperature

90

°C

Thermal resistivity of the soil

0.968

°C m/W

Current carrying capacity in the ground

68

A

Current carrying capacity in the duct

52

A