Parameters/Cases | Initial configured network Open Switch positions 69 70 71 72 73 | Optimal Reconfigured Network Open Switch positions 14 58 61 69 70 | ||||
---|---|---|---|---|---|---|
Case-1a | Case-2a | Case-3a | Case-1b | Case-2b | Case-3b | |
DG sizes in kW/Bus/power factor | 500/11/0.82 1652/61/0.81 500/18/0.89 | 2292/61/0.8 500/36/0.8 724/62/0.84 | 2405/61/0.8 503/22/0.96 604/49/0.92 | 1411/61/0.81 500/64/0.83 534/11/0.81 | 214/69/0.83 378/62/0.8 3207/61/0.83 | 500/64/0.84 500/11/0.84 2193/61/0.8 |
Minimum and Maximum voltage in p.u | 0.9943 & 1.0047 | 0.9818 & 1.0497 | 0.9972 & 1.0287 | 0.9938 & 1 | 0.9899 & 1.05 | 0.9936 & 1.0229 |
\(\lambda_{max}\) | 4.2 | 4.91 | 4.61 | 6.49 | 7.71 | 7.07 |
\(\lambda_{V}\) | 1.53 | 1.74 | 1.89 | 1.93 | 2.18 | 2.37 |
Real power loss in kW | 4.847 | 89.8601 | 30.2921 | 5.3082 | 93.9651 | 25.313 |
OF value | – | – | 0.1229 | – | – | 0.2254 |
% KVA DG INJECTION | 68.79 | 93.56 | 89.01 | 64.45 | 98.58 | 84.33 |
% PLR | 97.84 | 60.05 | 86.53 | 97.64 | 58.22 | 88.74 |
% MLI | 30.84 | 52.95 | 43.61 | 102.18 | 140.18 | 120.249 |