Parameters/Cases | Initial configured network Open Switch positions 33 34 35 36 37 | Optimal Reconfigured Network Open Switch positions 7 9 14 28 32 | ||||
---|---|---|---|---|---|---|
Case-1a | Case-2a | Case-3a | Case-1b | Case-2b | Case-3b | |
DG sizes in kW/Bus/ power factor | 1044/24/0.88 1156/30/0.8 737/14/0.88 | 1832/31/0.8 550/17/1 792/14/0.82 | 1009/15/0.89 837/7/0.8 1097/31/0.8 | 414/33/0.92 573/12/0.88 1520/29/0.8 | 356/32/0.8 2519/30/0.83 828/33/0.93 | 969/31/0.8 1164/29/0.8 564/33/0.91 |
Minimum and Maximum voltage in p.u | 0.9916 & 1.0007 | 0.9853 & 1.0498 | 0.9848 & 1.0371 | 0.9884 & 1.001 | 0.978 & 1.0495 | 0.9732 & 1.028 |
\(\lambda_{max}\) | 4.4 | 5.1 | 4.78 | 6.15 | 7.23 | 6.76 |
\(\lambda_{V}\) | 1.49 | 2.04 | 1.85 | 1.75 | 1.68 | 1.56 |
Real power loss in kW | 12.7458 | 86.5804 | 39.1317 | 18.7531 | 98.8904 | 42.7188 |
OF value | – | – | 0.1364 | – | – | 0.1894 |
% KVA DG INJECTION | 79.17 | 84.97 | 81.014 | 68.4 | 99.6 | 74.92 |
% PLR | 93.95 | 58.96 | 81.45 | 91.11 | 53.12 | 79.75 |
% MLI | 29.41 | 50 | 40.58 | 80.88 | 112.64 | 98.82 |