Table 3 Power factor and correction time of different load conditions with different controllers

From: Coordinated control of DSTATCOM with switchable capacitor bank in a secondary radial distribution system for power factor improvement

Loads

Quarter load (200 kW)

Half load (400 kW)

Control methods

no control

IRPT

ADALINE

SRFT

No control

IRPT

ADALINE

SRFT

Source Current (A) (RMS)

299

278.37

278.35

278.39

617

556.74

556.69

556.77

Response Time (ms)

–

28

22

29

–

48

46

71

Power Factor

0.93

0.9996

0.9996

0.9994

0.90

0.9996

0.9996

0.9995

Loads

3/4th Load (600 kW)

Full Load (800 kW)

Control methods

No control

IRPT

ADALINE

SRFT

No control

IRPT

ADALINE

SRFT

Source Current (A) (RMS)

982

1193.92

1193.84

1193.93

1357

1113.03

1113.01

1113

Response Time (ms)

–

47

44

50

–

47

44

49

Power Factor

0.85

0.9998

0.9999

0.9998

0.82

0.9999

0.9999

0.9999