Table 6 Voltage magnitude and angles at all buses for λ = 1.5

From: An efficient load flow solution for distribution system with addition of distributed generation using improved harmony search algorithms

Bus no.Loading parameter, λ = 1.5
NR methodBW/FW methodIHS
Voltage (p.u.)Angle (°)
1Fail to convergeFail to converge10
20.95916− 1.98214
30.922091− 5.43179
40.799481− 10.2382
50.728309− 11.738
60.597883− 17.2898
70.562162− 19.5731
80.507072− 21.9017
90.437166− 24.3146
100.400046− 24.9881