Skip to main content

Table 4 Voltage magnitude and angles at all buses for the base case

From: An efficient load flow solution for distribution system with addition of distributed generation using improved harmony search algorithms

Bus no.

NR and BW/FW method

IHS

Voltage (p.u.)

Angle (°)

Voltage (p.u.)

Angle (°)

1

1

0

 

0

2

0.993032

− 0.508712

1

− 0.55081

3

0.98759

− 1.234463

0.989369

− 1.39143

4

0.964189

− 2.260095

0.979776

− 2.35977

5

0.94927

− 2.563162

0.948125

− 2.51909

6

0.919731

− 3.575559

0.930275

− 3.08484

7

0.910303

− 3.963496

0.898919

− 3.28055

8

0.893342

− 4.405375

0.890072

− 3.43316

9

0.865907

− 5.092424

0.876492

− 3.63278

10

0.847727

− 5.564185

0.858537

− 3.81925