Skip to main content

Table 2 Voltage magnitude and angles at all buses for loading parameter 0.5 and 1

From: An efficient load flow solution for distribution system with addition of distributed generation using improved harmony search algorithms

Bus no.λ = 0.5λ = 1 (NR method fails to converge)
NR and BW/FW methodIHSBW/FW methodIHS
Voltage (p.u.)Angle (°)Voltage (p.u.)Angle (°)Voltage (p.u.)Angle (°)Voltage (p.u.)Angle (°)
110101010
20.988207− 0.814060.982343− 0.863740.980966− 1.184180.975082− 1.28949
30.97871− 2.010640.965682− 2.240050.964776− 3.011040.952839− 3.36755
40.939225− 3.717020.912916− 3.819570.901417− 5.611170.877246− 6.06612
50.913865− 4.237580.884249− 4.118780.860521− 6.411190.832885− 6.71287
60.862084− 6.031420.836185− 5.35710.773552− 9.348630.749184− 9.01488
70.845068− 6.754830.823158− 5.850710.743988− 10.62560.724111− 9.93988
80.814016− 7.601610.801054− 6.430890.689626− 12.13930.681141− 10.8925
90.761801− 9.05090.766397− 7.408660.595288− 15.05870.609781− 12.5176
100.725008− 10.19610.740121− 8.244540.527498− 17.74480.557307− 14.0489