51-node distribution system | Methodology proposed in [4] | Methodology proposed in [9] | Sensitivity analysis method [22] (0.95 lag pf DGs and SCs) | Proposed simultaneous optimization method (0.95 lag pf DGs and SCs) |
---|---|---|---|---|
S/S active power (kW) | 1229.92 | 1047.61 | 1361.46 | 1029.87 |
S/S reactive power (kVAR) | 791.45 | 611.55 | 768.23 | 529.57 |
Real power loss (kW) | 36.10 | 59.59 | 67.69 | 34.29 |
Reactive power loss (kVAR) | 22.45 | 63.61 | 33.55 | 17.91 |
Voltage (V(p.u)) (minimum) | 0.9711 (V51) | 0.9615 (V45) | 0.9684 (V39) | 0.9743 (V51) |
Voltage stability index | 0.0362 | 0.0362 | 0.0363 | 0.0361 |