69-node distribution system | Sensitivity analysis [22] | Simultaneous optimization-based method | ||||
---|---|---|---|---|---|---|
upf DGs and shunt capacitors | 0.95 lag pf DGs only | 0.95 lag pf DGs and shunt capacitors | upf DGs and shunt capacitors | 0.95 lag pf DGs only | 0.95 lag pf DGs and shunt capacitors | |
S/S active power (kW) | 1607.72 | 1576.86 | 1609.18 | 1584.90 | 1563.62 | 1577.89 |
S/S reactive power (kVAR) | 1146.58 | 1974.11 | 1133.68 | 1131.90 | 1966.81 | 594.04 |
Real power loss (kW) | 50.95 | 55.87 | 49.42 | 19.18 | 33.69 | 15.15 |
Reactive power loss (kVAR) | 26.98 | 29.34 | 26.17 | 12.30 | 19.09 | 10.55 |
Voltage (V(p.u)) (minimum) | 0.9756 (V27) | 0.9732 (V27) | 0.9756 (V27) | 0.9859 (V65) | 0.9810 (V65) | 0.9850 (V27) |
Voltage stability index | 0.0196 | 0.0197 | 0.0196 | 0.0154 | 0.0156 | 0.0153 |