Skip to main content

Table 6 Performance of 69-node distribution system

From: Simultaneous optimal allocation and sizing of distributed generations and shunt capacitors in distribution networks using fuzzy GA methodology

69-node distribution system

Sensitivity analysis [22]

Simultaneous optimization-based method

upf DGs and shunt capacitors

0.95 lag pf DGs only

0.95 lag pf DGs and shunt capacitors

upf DGs and shunt capacitors

0.95 lag pf DGs only

0.95 lag pf DGs and shunt capacitors

S/S active power (kW)

1607.72

1576.86

1609.18

1584.90

1563.62

1577.89

S/S reactive power (kVAR)

1146.58

1974.11

1133.68

1131.90

1966.81

594.04

Real power loss (kW)

50.95

55.87

49.42

19.18

33.69

15.15

Reactive power loss (kVAR)

26.98

29.34

26.17

12.30

19.09

10.55

Voltage (V(p.u)) (minimum)

0.9756 (V27)

0.9732 (V27)

0.9756 (V27)

0.9859 (V65)

0.9810 (V65)

0.9850 (V27)

Voltage stability index

0.0196

0.0197

0.0196

0.0154

0.0156

0.0153